15 Analog I/O Function
15-12
CP1E CPU Unit Software User’s Manual(W480)
15-3 I/O Allocation and Related Auxiliary
Area Flags
15-3-1 I/O Allocation
Word I/O Points Description Values
CIO 90 AD0 CIO words that I/O conversion data for AD0 is
stored in.
-10V to 10V range: F448 to
0BB8 hex
Other ranges: 0000 to 1770 hex
CIO 91 AD1 CIO words that I/O conversion data for AD1 is
stored in.
CIO 190 DA0 CIO words that I/O conversion data for DA0 is
stored in.
15-3-2 Related Auxiliary Area Flags
Bit Name Description Values
A434.00 Open-circuit
Detection Flags
When analog Input 0 (AD0) open-circuit Error
is detected, this bit will be changed to “1”.
0: No error
1: Open-circuit error detected
A434.01 Open-circuit
Detection Flags
When analog Input 1 (AD1) open-circuit Error
is detected, this bit will be changed to “1”.
A434.04 Analog Initial-
ization Com-
pleted Flag
The Analog Initialization Completed Flag will
be changed to “1” ON when initial processing
is completed.
If the system starts operating, use this flag in
the program to delay reading converted data
from analog inputs until the data is valid.
0: Initializing
1: Initialization completed
A315.14 Built-in Analog
Error
When the built-in analog do not work normally,
this bit will be changed to “1”.
0: No error
1: Built-in analog error