17 Ethernet Option Board
17-26
CP1E CPU Unit Software User’s Manual(W480)
When displaying 0000, the port number is 9600.
The IP address is (1)(2).(3)(4).(5)(6).(7)(8) (hex)
Mode Setting
Bit Mode Settings
0 Reserved Always 0.
1 Broadcast address 0: 4.3BSD specifications
1: 4.2BSD specifications
2 to 3 IP address conversion method 00, 01: Automatic generation method
10: IP address table reference method
11: Combined method
4 FINS/UDP port number 0: Default (9600)
1: Unit setup value
5 FINS/TCP port number 0: Default (9600)
1: Unit setup value
6 FINS/UDP destination IP mode 0: Enable (Dynamically)
1: Disable (Static)
7 FINS/TCP protect function 0: Disable (Only FINS/TCP Server)
1: Enable (Only FINS/TCP Server)
8 to 15 Reserved Always 0.
FINS/TCP and FINS/UDP Port Number
IP Address
D1300
1514131211109876543210
00000000 0
Broadcast address
IP address conversion method
FINS/UDP port number
FINS/UDP destination IP mode
FINS/TCP protect function
FINS/TCP port number
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
D1301
D1302
FINS/TCP port number (hex)
FINS/UDP port number (hex)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
D1303
D1304
(1)(2) (3)(4)
(5)(6) (7)(8)