17 Ethernet Option Board
17-36
CP1E CPU Unit Software User’s Manual(W480)
17-6 Connection Method with the
CX-Programmer
The CX-Programmer version 9.12 or higher can be connected online to the Ethernet Option Board with
Ethernet. The connection method shows below.
In the following example, the Ethernet Option Board is connected without making any setting.
Precautions for Correct UsePrecautions for Correct Use
Confirm the Communications Settings on the Serial Option Port Tab in the PLC Settings Dialog
Box of the CP1E CPU Unit. If the mode is set to Host Link and the baud rate to 9,600 or other
values except 115,200, the CP1E CPU Unit cannot be connected with Ethernet. ERR LED of the
Ethernet Option Board will be lit. Change the PLC Settings by USB port.
Example
Computer Ethernet Option Board
IP address 192.168. 250.A
(Set by manual on Windows)
192.168. 250.1
(Default)
Decision direction ↓↑
FINS node address A
(Auto-generation in the
CX-Programmer)
1
(Default)
Computer CX-Programmer
Ethernet
Default: 1
Set to 192.168. 250. A (A is any value except 1)
Set IP address in Windows’ Local Area Connection
Properties – Internet Protocol (TCP/IP) - Properties
A (except 1)
Display in Workstation Node Number on the Network
Type Tab in CX-Programmer’s Change PLC Dialog
Box
Ethernet Option Board
FINS node address
IP address
Default: 192.168. 250. 1
Auto-generation in the CX-Programmer
Select Auto-detect in Workstation Node
Number
Network typeEthernet