18 Programming Device Operations
18-26
CP1E CPU Unit Software User’s Manual(W480)
Additional Information
Select On to turn ON a bit and Off to turn OFF a bit.
To cancel forced status, select Cancel.
A ladder program running on the CP1E can be edited online.
This can be done while the CP1E is in MONITOR mode or PROGRAM mode.
Using the CX-Programmer, it is possible to either change part of a ladder program running on the CP1E , or
make an addition to the program.
Online editing is used to make minor changes to the ladder program without actually stopping the oper-
ation of the CP1E.
Precautions for Correct UsePrecautions for Correct Use
When a ladder program has been changed using online editing, the cycle time may increase
by one or more cycles, or it may not be possible to read an input signal.
Major changes, such as moving a rung, copying, inserting, or deleting, should be done offline
and then the program should be transferred to the CP1E again.
After completing online editing, the results of editing are backed up to backup memory, result-
ing in a longer cycle time. While this is being done, the BKUP indicator will be lit, and the
CX-Programmer will indicate the progress.
An increase of one cycle will be 16ms maximum daring online editing and 8% of cycle time
during back up.
3
Right-click and select Force - On.
The input bit will be force-set. A
symbol indicating the force-set sta-
tus will be displayed at the input con-
dition.
18-5-3 Online Editing