14 Serial Communications
14-6
CP1E CPU Unit Software User’s Manual(W480)
Set the parameters in the PLC Setup and the PT’s System Menu.
Click the Built-in RS232C Port or Serial Option Port Tab in the PLC Settings Dialog Box.
14-2-2 Flow of Connection
CP1E CPU Unit PT (e.g. NS-series)
1
2
3
4
5
14-2-3 PLC Setup and PT System Settings
PLC Setup
Connect the CP1E CPU Unit and external devices using the RS-232C or RS-422A/485 ports.
CX-Designer
Transfer the PLC Setup.
NS-series PT
System Menu
Set the same communications settings in the CP1E CPU Unit’s PLC Setup and in the NS-series PT.
PLC Setup
Select Built-in RS232C Port or Serial
Option Port in the PLC Setup of the CP1E
CPU Unit using the CX-Programmer. Set
the serial communications mode to NT
Link (1:N), set the baud rate, and set the
highest unit number to at least 1.
Create a project using the CX-
Designer and select Serial Port A or
Serial Port B in the communications
settings.
Transfer screen
Transfer screen data created
using the CX-Designer to the NS-
series PT.
Check the communications settings
in the NS-series PT on the Comm
Settings Tab Page in the system
menu.