EasyManua.ls Logo

Omron CP1E CPU UNIT SOFTWARE - Analog Input and Output Signal Ranges; Analog Input Signal Ranges

Omron CP1E CPU UNIT SOFTWARE
450 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15-7
15 Analog I/O Function
CP1E CPU Unit Software User’s Manual(W480)
15-2 Analog Input and Output Signal Ranges
15
15-2-1 Analog Input Signal Ranges
15-2 Analog Input and Output Signal Ranges
Analog I/O data is digitally converted according to the analog I/O signal range as shown below.
Note When the input exceeds the specified range, the AD converted data will be fixed at either the lower limit or
upper limit.
-10 to 10 V Input
When the resolution is set to 1/6,000, the -10 to 10-V range corresponds to hexadecimal values
F448 to 0BB8 (-3,000 to 3,000). The entire data range is F31C to 0CE4 (-3,300 to 3,300).
A negative voltage is expressed as a two’s complement.
0 to 10 V Input
When the resolution is set to 1/6,000, the 0 to 10-V range corresponds to hexadecimal values 0000
to 1770 (0 to 6,000). The entire data range is FED4 to 189C (-300 to 6,300).
A negative voltage is expressed as a two’s complement.
15-2-1 Analog Input Signal Ranges
0 V 10 V
11 V
11 V
10 V
F448 (3000)
F31C (3300)
0CE4 (3300)
0BB8 (3000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
0 V 10 V
10.5 V
0.5 V
FED4 (300)
189C (6300)
1770 (6000)
0000 (0)
Converted Data
Hexadecimal (Decimal)

Table of Contents