15-9
15 Analog I/O Function
CP1E CPU Unit Software User’s Manual(W480)
15-2 Analog Input and Output Signal Ranges
15
15-2-2 Analog Output Signal Ranges
4 to 20 mA
When the resolution is set to 1/6,000, the 4- to 20-mA range corresponds to hexadecimal values
0000 to 1770 (0 to 6,000). The entire data range is FED4 to 189C (-300 to 6,300).
Inputs between 3.2 and 4 mA are expressed as two’s complements. If the input falls below 3.2 mA,
open-circuit detection will activate and converted data will be 8000.
-10 to 10 V Outputs
When the resolution is set to 1/6,000, the hexadecimal values F448 to 0BB8 (-3,000 to 3,000) corre-
spond to an analog voltage range of -10 to 10 V.
Specify a negative voltage as a two’s complement.
0 to 10 V Outputs
When the resolution is set to 1/6,000, the hexadecimal values 0000 to 1770 (0 to 6,000) correspond
to an analog voltage range of 0 to 10 V.
Specify a negative voltage as a two’s complement.
15-2-2 Analog Output Signal Ranges
4 mA 20 mA
20.8 mA
3.2 mA
FED4 (300)
189C (6300)
1770 (6000)
0000 (0)
0 mA
Converted Data
Hexadecimal (Decimal)
0 V
10 V
11 V
11 V
10 V
F448
(3000)
F31C
(3300)
0CE4
(3300)
0BB8
(3000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
0 V
10 V
10.5 V
0.5 V
FED4
(300)
189C
(6300)
1770
(6000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)