7 PLC Setup
7-16
CP1E CPU Unit Software User’s Manual(W480)
Origin Return Settings
Name Default Possible settings
When setting is read by
CPU Unit
1 Speed 0 pps (disabled) 1 pps At start of operation
:
100,000 pps
2 Acceleration Ratio (rate) 0 (disabled) 1 (pulse/4 ms) At start of operation
:
65,535 (pulse/4 ms)
3 Deceleration rate 0 (disabled) 1 (pulse/4 ms) At start of operation
:
65,535 (pulse/4 ms)
7-2-9 Built-in AD/DA: Built-in Analog I/O Settings
AD 0CH/AD 1CH: Analog Input Settings
Name
Default
Possible settings
When setting is read by
CPU Unit
1 Analog Input 0: Use Do not use. Do not use. When power is turned ON
Use.
1-1 Range -10 to 10 V -10 to 10 V When power is turned ON
0 to 10 V
1 to 5 V
0 to 5 V
0 to 20 mA
4 to 20 mA
1-2 Use averaging Do not use. Do not use. When power is turned ON
Use.
2 Analog Input 1: Use Do not use. Do not use. When power is turned ON
Use.
2-1 Range -10 to 10 V -10 to 10 V When power is turned ON
0 to 10 V
1 to 5 V
0 to 5 V
0 to 20 mA
4 to 20 mA
2-2 Use averaging Do not use Do not use. When power is turned ON
Use.
DA 0CH: Analog Output Settings
Name
Default
Possible settings
When setting is read by
CPU Unit
1 Analog Output 0: Use Do not use. Do not use. When power is turned ON
Use.
1-1 Range -10 to 10 V -10 to 10 V When power is turned ON
0 to 10 V
1 to 5 V
0 to 5 V
0 to 20 mA
4 to 20 mA