14 Serial Communications
14-22
CP1E CPU Unit Software User’s Manual(W480)
Built-in RS232C Port or Serial Option Port Tab Page
Built-in RS232C Port or Serial Option Port Tab Page
Parameter Setting
Communications Settings Set the communications settings to the same values as the connected
PLCs.
If the connected PLCs are set to 115,200 bps, select the Custom Option,
set the baud rate to 115200. The format can be set to any value.
Mode Select PC Link (Master).
Link Words Set to 10 (default) for the Master only. 10 words (default)
PC Link Mode Select All or Master.
NT/PC Link Max. Set the highest unit number of the connected slaves.
Settings at the Polled Unit
Parameter Setting
Communications Settings Set the communications settings to the same values as the connected
PLCs.
If the connected PLCs are set to 115,200 bps, select the Custom Option,
set the baud rate to 115200. The format can be set to any value.
Mode Select PC Link (Slave).
PC Link Unit No. Set the unit number (0 to 7).