17 Ethernet Option Board
17-14
CP1E CPU Unit Software User’s Manual(W480)
The FINS node address of the Ethernet Option Board is factory-set to 1.
It can be changed in the Settings from the Web browser. The setting range is 1 to 254.
The IP address of the Ethernet Option Board (Local IP address) is factory-set to 192.168.250.1.
Local IP address can be set by the following two methods.
Method 1: Set in the Settings from the Web browser
Method 2: Set to 0.0.0.0 from the Web browser, and then set in the allocated words in the DM area
(D1355 and D1356) by the ladder programmer
If the local IP address is set neither by method 1 nor by method 2 (at default settings), it remains
192.168.250.1.
Confirmation on Local IP Address
The local IP address can be confirmed in the allocated words in the DM area (D1355 and D1356),
when the power of the PLC is turned OFF and then ON again.
FINS Node Address of the Ethernet Option Board
Local FINS Node Address=1
IP Address of the Ethernet Option Board
Local IP Address=192.168.250.1
Factory setting
192.168.250.1
When setting neither in the
allocated words in the DM area
nor by the Web browser function
Remains the default setting
192.168.250.1
Except 192.168.250.1
Method 1: Set by the Web browser
function
IP address
Method 2: Set to 0.0.0.0 from the Web
browser, and then set in the allocated
words in the DM area
It is the IP address set in the
Settings from the Web browser
It is the IP address set in the allocated
words in the DM area (D1355, D1356)
IP ADDRESS:
SUBNET MASK:
COMM ERR
10BASE-T
100BASE-TX