17 Ethernet Option Board
17-34
CP1E CPU Unit Software User’s Manual(W480)
03C3 --- FINS/UDP Packet
discarded
00 01 to FE
Node address
The automatic genera-
tion (static) method was
used as the IP address
conversion method, so
remote IP address infor-
mation in internal memory
could not be changed.
---
03C8 --- Socket Error Arbitrary Resend the packet or the
destination node is not in
the network.
---
03D0 FLASH System setup sum
value error
Reset the value of system
setup area, Restart CPU
Unit.
Saved
0601 LIT Option Board error Arbitrary Restart the CPU Unit. If
the problem persists,
replace the Ethernet
Option Board.
Saved
0602 LIT Option Board mem-
ory error
01: Read error
02: Write error
06: Error log Restart the CPU Unit. If
the problem persists,
replace the Ethernet
Option Board.
Saved
(except
error log)
--- FLASH Serial Option Port
Communications Set-
tings error
Set the PLC Settings on
the Serial Option Port Tab
as follows, and then turn
the power ON again.
Communications Settings
Baud: 115200
Format: 7, 2, E
Mode: Host Link
---
Error
code
ERR
LED
Meaning
Detailed error code
Correction EEPROM
1st byte 2nd byte