Appendices
A-60
CP1E CPU Unit Software User’s Manual(W480)
A300 Error Log Pointer When an error occurs, the Error Log
Pointer is incremented by 1 to indicate
the location where the next error record
will be recorded as an offset from the
beginning of the Error Log Area (A100
to A199).
Note 1 The data will be unstable if the
capacitor becomes
discharged.
2 The Error Log Pointer can be
cleared to 00 by turning
A500.14 (the Error Log Reset
Bit) ON.
3 When the Error Log Pointer
has reached 14 hex (20 deci-
mal), the next record is stored
in A195 to A199 when the next
error occurs.
00 to 14 hex Retained Retained Refreshed
when error
occurs.
A500.14
A310 Manufacturing Lot
Number, Lower Digits
The manufacturing lot number is stored
in 6 digits hexadecimal. X, Y, and Z in
the lot number are converted to 10, 11,
and 12, respectively.
Examples:
Lot number 01805
A310 = 0801, A311 = 0005
Lot number 30Y05
A310 =1130, A311 = 0005
Retained Retained
A311 Manufacturing Lot
Number, Upper Digits
A315 13 Option Board Error
Flag
ON when the Option Board is removed
while the power is being supplied. CPU
Unit operation will continue and the
ERR/ALM indicator will flash.
Note OFF when the error has been
cleared.
Cleared Cleared Refreshed
when a
non-fatal error
occurs.
A402.00,
A424
14 Built-in Analog I/O
Error Flag
ON when a built-in analog I/O error
occurs and stops the operation of
built-in analog I/O. CPU Unit operation
will continue and the ERR/ALM indica-
tor will flash. OFF when the error has
been cleared.
Cleared Cleared Refreshed
when a
non-fatal error
occurs.
A402.00
15 Backup Memory Error
Flag
ON when writing to the built-in
EEPROM backup memory fails. CPU
Unit operation will continue and the
ERR/ALM indicator will flash.
Note OFF when the error has been
cleared.
Cleared Cleared Refreshed
when a
non-fatal error
occurs.
A402.00
A316 to
A317
High-speed Counter 2
PV
Contains the PV of high-speed counter
2.
• The PV is cleared when operation
starts.
A317 contains the upper 4 digits and
A316 contains the lower 4 digits.
Cleared • Refreshed
each cycle
during the
overseeing
processes.
• Refreshed
when PRV
instruction is
executed to
read PV.
A318 to
A319
High-speed Counter 3
PV
Contains the PV of high-speed counter
3.
• The PV is cleared when operation
starts.
A319 contains the upper 4 digits and
A318 contains the lower 4 digits.
Cleared • Refreshed
each cycle
during the
overseeing
processes.
• Refreshed
when PRV
instruction is
executed to
read PV.
Address
Name Function Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words Bits