Appendices
A-62
CP1E CPU Unit Software User’s Manual(W480)
A321 08 High-speed Counter 3
Comparison
In-progress Flag
This flag indicates whether a compari-
son operation is being executed for
high-speed counter 3.
Cleared when operation starts.
OFF: Stopped.
ON: Being executed
Cleared Refreshed
when compari-
son operation
starts or stops.
09 High-speed Counter 3
Overflow/Underflow
Flag
This flag indicates when an overflow or
underflow has occurred in the
high-speed counter 3 PV. (Used with
the linear mode counting range only.)
Cleared when operation starts.
Cleared when the PV is changed.
OFF: Normal
ON: Overflow or underflow
Cleared Refreshed
when an over-
flow or under-
flow occurs.
10 High-speed Counter 3
Count Direction
This flag indicates whether the
high-speed counter is currently being
incremented or decremented. The
counter PV for the current cycle is com-
pared with the PV in last cycle to deter-
mine the direction.
OFF: Decrementing
ON: Incrementing
Cleared Setting used
for high-speed
counter, valid
during counter
operation.
A322 to
A323
High-speed Counter 4
PV
Contains the PV of high-speed counter
4.
The PV will be cleared at the start of
operation.
A323 contains the upper four digits and
A322 contains the lower four digits.
Cleared Refreshed
each cycle
during the
overseeing
processes.
Refreshed
when PRV
instruction is
executed to
read PV.
A324 to
A325
(Not
sup-
ported
by E10
CPU
Unit)
High-speed Counter 5
PV
Contains the PV of high-speed counter
5.
The PV is cleared when operation
starts.
A325 contains the upper 4 digits and
A324 contains the lower 4 digits.
Cleared Refreshed
each cycle
during the
overseeing
processes.
Refreshed
when PRV
instruction is
executed to
read PV.
A326 00 High-speed Counter 4
Range 1 Comparison
Condition Met Flag
These flags indicate whether the PV is
within the specified ranges when
high-speed counter 4 is being operated
in range-comparison mode for upper
and lower limits.
Cleared when operation starts.
Cleared when range comparison
table is registered.
OFF: PV not in range
ON: PV in range
Cleared Refreshed
each cycle
during the
overseeing
processes.
Refreshed
when PRV
instruction is
executed to
read the
results of
range com-
parison.
01 High-speed Counter 4
Range 2 Comparison
Condition Met Flag
02 High-speed Counter 4
Range 3 Comparison
Condition Met Flag
03 High-speed Counter 4
Range 4 Comparison
Condition Met Flag
04 High-speed Counter 4
Range 5 Comparison
Condition Met Flag
05 High-speed Counter 4
Range 6 Comparison
Condition Met Flag
Address
Name Function Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words Bits