A-77
Appendices
CP1E CPU Unit Software User’s Manual(W480)
A-2 Auxiliary Area Allocations by Address
App
A-2-2 Read/Write Words
A642 Analog Adjustment 1
PV
Stores the value set on analog
adjuster 1 as a hexadecimal value.
0000 to 00FF hex Retained Cleared
A643 Analog Adjustment 2
PV
Stores the value set on analog
adjuster 2 as a hexadecimal value.
0000 to 00FF hex Retained Cleared
A720
to
A722
(CP1E
N/NA-
type
CPU
Unit
only)
Power ON Clock Data
1
These words contain the time at which
the power was turned ON one time
before the startup time stored in words
A510 to A511.
A720.00 to A720.07: Seconds (00 to
59)
A720.08 to A720.15: Minutes (00 to
59)
A721.00 to A721.07: Hour (00 to 23)
A721.08 to A721.15: Day of month (01
to 31)
A722.00 to A722.07: Month (01 to 12)
A722.08 to A722.15: Year (00 to 99)
Note 1 All of the clock data from
A720 to A749 is cleared if the
capacitor becomes
discharged.
2 In an E-type CPU Unit, or if
the clock data is not set for an
N/NA-type CPU Unit, the data
will be for 1:01.01 on Sunday
January 1, 2001.
See at left. Retained Retained Written when
power is
turned ON.
A723
to
A725
(CP1E
N/NA-
type
CPU
Unit
only)
Power ON Clock Data
2
These words contain the time at which
the power was turned ON two times
before the startup time stored in words
A510 to A511.
A723.00 to A723.07: Seconds (00 to
59)
A723.08 to A723.15: Minutes (00 to
59)
A724.00 to A724.07: Hour (00 to 23)
A724.08 to A724.15: Day of month (01
to 31)
A725.00 to A725.07: Month (01 to 12)
A725.08 to A725.15: Year (00 to 99)
See at left. Retained Retained Written when
power is
turned ON.
A726
to
A728
(CP1E
N/NA-
type
CPU
Unit
only)
Power ON Clock Data
3
These words contain the time at which
the power was turned ON three times
before the startup time stored in words
A510 to A511.
A726.00 to A726.07: Seconds (00 to
59)
A726.08 to A726.15: Minutes (00 to
59)
A727.00 to A727.07: Hour (00 to 23)
A727.08 to A727.15: Day of month (01
to 31)
A728.00 to A728.07: Month (01 to 12)
A728.08 to A728.15: Year (00 to 99)
See at left. Retained Retained Written when
power is
turned ON.
A729
to
A731
(CP1E
N/NA-
type
CPU
Unit
only)
Power ON Clock Data
4
These words contain the time at which
the power was turned ON four times
before the startup time stored in words
A510 to A511.
A729.00 to A729.07: Seconds (00 to
59)
A729.08 to A729.15: Minutes (00 to
59)
A730.00 to A730.07: Hour (00 to 23)
A730.08 to A730.15: Day of month (01
to 31)
A731.00 to A731.07: Month (01 to 12)
A731.08 to A731.15: Year (00 to 99)
See at left. Retained Retained Written when
power is
turned ON.
Address
Name Function Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words Bits

Table of Contents