371
Sample Programs Appendix B
Program Example
• Data Flow (Unit Number 0): Word 2001 (AD Conversion Value)
→ D00001 (Mean Value Result)
Limit
If the output value range is exceeded, the output voltage is held when the Conversion Enable Flag turns OFF.
Unit Settings
Program Example
DM Area Settings
Item Setting contents Actual settings
Unit CS1W-DA08V ---
Unit number #0 Unit number switch: 00
Operation mode Normal mode Back-panel DIP switch: All OFF
Output number Output 1 used D20000 = 0001
Output signal range All output numbers, 0 to 10 V D20001 = 0001
Output hold function HOLD D20002 = 0001
AVG(195)
2001
#0064
D00001
Execution condition
Conversion value
Number of samplings
Mean value
5 V (03E8)
0 V (0000)
Set value
Actual output value
When program is started
MOV(021)
D00000
2001
Execution condition
Set value
<
2001
D00000
Set value
Lower limit
Conversion Enable
Flag for output 1
>
2001
D00001
Set value
Upper limit
200000
D00001: 0000
D00002: 03E8
Lower limit: 0 V
Upper limit: 5 V