6 - 55
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-7 Initial Setting Level
6
o1th
Simple Transfer Output 1 Upper
Limit
The E5CC-U or E5GC must be used.
There must be a linear current output.
The Control Output 1 Assignment parameter must
specify the simple transfer SP, simple transfer
ramp SP, simple transfer PV, simple transfer MV
(heating), or simple transfer MV (cooling).
o1tl
Simple Transfer Output 1 Lower
Limit
• This parameter sets the upper and lower limit values for simple transfer output 1.
* The E5CC-U must be manufactured in May 2014 or later (version 2.2 or higher).
* This function can be set for standard control, but the setting will be disabled.
z Related Parameter
Control Output 1 Assignment (Advanced Function Setting Level): Page 6-79
Function
Setting
Transfer
output type
Setting range
Default
Unit
Transfer output
lower limit
Transfer output
upper limit
Simple
transfer SP
SP lower limit to SP upper limit SP lower limit SP upper limit EU
Simple
transfer
ramp SP
SP lower limit to SP upper limit
Simple
transfer PV
Temperature
input
Input setting range
lower limit to input
setting range upper
limit
Input setting
range lower limit
Input setting
range upper
limit
Analog input Analog scaling
lower limit to analog
scaling upper limit
Scaling lower
limit
Scaling upper
limit
Simple
transfer MV
(heating)
Standard −5.0 to 105.0 0.0 100.0 %
Heating/
cooling
0.0 to 105.0
Simple
transfer MV
(cooling)*
See
See