140
Logic Operations Section 4-22
3. Select Library 1 from the library list, and then click the
OK Button.
Confirm the following settings, and then click the OK
Button.
Work bit 1 operation type: Operation 1
Work bit 1 input assignment A = 7: Alarm 1
Work bit 1 input assignment B = 19: Invert for RUN/
STOP
Work bit 1 input assignment C = 0: Always OFF
Work bit 1 input assignment D = 0: Always OFF
Auxiliary output 1 = Work bit 1
4. Closing the Logic Operation Editor Dialog Box
Click the Close Button.
This completes the procedure for setting parameters
using the CX-Thermo. Transfer the settings to the Control-
ler to set the Controller. Refer to CX-Thermo help for the
procedure to transfer the settings.