140
Logic Operations Section 4-22
3. Select Library 1 from the library list, and then click the
OK Button.
Confirm the following settings, and then click the OK
Button.
Work bit 1 operation type: Operation 1
Work bit 1 input assignment A = 7: Alarm 1
Work bit 1 input assignment B = 19: Invert for RUN/
STOP
Work bit 1 input assignment C = 0: Always OFF
Work bit 1 input assignment D = 0: Always OFF
Auxiliary output 1 = Work bit 1
4. Closing the Logic Operation Editor Dialog Box
Click the Close Button.
This completes the procedure for setting parameters
using the CX-Thermo. Transfer the settings to the Control-
ler to set the Controller. Refer to CX-Thermo help for the
procedure to transfer the settings.

Table of Contents

Other manuals for Omron E5CN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN and is the answer not in the manual?

Omron E5CN Specifications

General IconGeneral
CommunicationRS-485 (optional)
MountingPanel Mount
Control MethodON/OFF
Input TypeThermocouple, RTD
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage (for driving SSR), Current
Display Type7-segment LED
Size48 x 48 mm
Control OutputRelay, Voltage (for driving SSR), Current
Alarm Output1 or 2 outputs
Dimensions48 x 48 x 78 mm
Ambient Operating Temperature-10 to 55°C
Protection RatingIP66

Related product manuals