Advanced Function Setting Level Section 5-8
The setting of this parameter determines when ST operates.
This parameter cannot be used when ST is set to OFF.
Related Parameters
Input type: Page 184, PID ON/OFF: Page 188, ST: Page 189 (initial setting
level)
Normally, use the default for this parameter.
This parameter sets the 2-PID control
α constant.
Related Parameters
PID ON/OFF: Page 188, ST: Page 189 (initial setting level)
st-b ST Stable Range
ST must be ON and temperature
input, standard control, 2-PID control
must be set.
Setting range Unit Default
0.1 to 999.9 °C or °F15.0
Function
Setting
See
See
alfa α
ST must be OFF and 2-PID control
must be set.
Setting range Unit Default
0.00 to 1.00 None 0.65
Function
Setting
See
See