Advanced Function Setting Level Section 5-8
This parameter sets the hysteresis for HS alarms.
Related Parameters
HS alarm use (advanced function setting level): Page 216
This parameter enables or disables the LBA function and sets the detection
time interval.
Set the time interval for detecting loop burnouts.
To disable the LBA function, set 0.
Related Parameters
Alarm 1 type (initial setting level): Page 191
LBA level: Page 218, LBA band: Page 218 (advanced function setting level)
hsh HS Alarm Hysteresis
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The HS Alarm parameter must be
set to ON.
The HS Alarm Latch parameter must
be set to OFF.
Setting range Unit Default
0.1 to 50.0 A 0.1
Function
Setting
See
See
lba LBA Detection Time
Alarm 1 must be assigned.
The alarm type must be set to 12
(LBA).
Setting range Unit Default
0 to 9999 Second 0
Function
Setting
See
See