268
Appendix
Dead Band c-db Universal input: −199.9 to
999.9
0.0 °C or °F
(See note
1.)
Analog input: −19.99 to 99.99 0.00 %FS
Manual Reset Value of-r 0.0 to 100.0 50.0 %
Hysteresis (Heating) hys Universal input: 0.1 to 999.9 1.0 °C or °F
(See note
1.)
Analog input: 0.01 to 99.99 0.10 %FS
Hysteresis (Cooling) chys Universal input: 0.1 to 999.9 1.0 °C or °F
(See note
1.)
Analog input: 0.01 to 99.99 0.10 %FS
Soak Time soak 1 to 9,999 1 min or h
Wait Band wt-b Universal input: OFF, 0.1 to
999.9
off, 0.1 to
999.9
OFF °C or °F
(See note
1.)
Analog input: OFF, 0.01 to
99.99
off, 0.01 to
99.99
OFF %FS
MV at Stop mv-s −5.0 to 105.0 (standard)
−105.0 to 105.0 (heating/cool-
ing)
0.0 %
MV at PV Error mv-e −5.0 to 105.0 (standard)
−105.0 to 105.0 (heating/cool-
ing)
0.0 %
SP Ramp Set Value sprt OFF or 1 to 9,999 off, 1 to
9999
OFF EU/s, EU/
min, EU/h
MV Upper Limit ol-h MV lower limit +0.1 to 105.0
(standard)
0.0 to 105.0 (heating/cooling)
105.0 %
MV Lower Limit ol-l −5.0 to MV upper limit −0.1
(standard)
−105.0 to 0.0 (heating/cool-
ing)
−5.0 (stan-
dard)
−105.0
(heating/
cooling)
%
MV Change Rate
Limit
orl 0.0 to 100.0
(0.0: MV Change Rate Limit
Disabled)
0.0 %/s
Extraction of Square
Root Low-cut Point
sqrp 0.0 to 100.0 0.0 %
Parameters Characters Setting (monitor) value Display Default Unit Set value