12 Troubleshooting and Maintenance
12 - 12
GX-series EtherCAT Slave Unit User’s Manual
Encoder Input Slave Unit
Some functions are not
reflected even after
parameters have been
set.
Parameters that are
enabled at the timing that
the count status changes
from disabled to enabled
were changed.
When the count is
enabled, execute the
count enable command
after the count disable
command. When the
count is disabled, execute
the count enable
command.
At preset execution,
"present value preset
execution completion" is
not turned ON, but
"present value preset set
value error" is turned ON.
It is attempted to preset
with a counter value
greater than the maximum
Circular Counter value.
Reset the preset
command value to equal
to or less than the
maximum Circular
Counter value and
execute the preset again.
Moreover, "present value
preset set value error" is
turned OFF when the
present value internal
reset is executed or
external reset is
generated.
Slave Unit type Symptom Cause Measures

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron GX-ID1611 and is the answer not in the manual?

Omron GX-ID1611 Specifications

General IconGeneral
BrandOmron
ModelGX-ID1611
CategoryTouch terminals
LanguageEnglish

Related product manuals