GX-series EtherCAT Slave Unit User’s Manual
Rated output current of 4.0 mA/common
I/O power supply current consumption of 10 mA max. (at 20.4 to 26.4 VDC).
Also, relays are two-wire output devices, so there is no output device current consumption.
Therefore,
I/O power supply current supplied to V and G terminals =10 mA + (20 mA × 5 points) =
110 mA < 4.0 A/common