EasyManuals Logo

Omron NS - SETUP User Manual

Omron NS - SETUP
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #125 background imageLoading...
Page #125 background image
4-2 1:N Host Connection
4-9
Setting the Communications Board Switches
• Using RS-422A
Set the switches of the C200HX/HG/HE(-Z) Communications Board, as follows:
Switch 1: 4
(Four-wire method = RS-422A)
Switch 2: ON (terminator ON = terminating resistance used)
Set the switches of the CQM1H Serial Communications Board as follows:
Two-wire/four-wire switch (WIRE): 4
(Four-wire method = RS-422A)
Terminating resistance switch (TERM): ON (terminator ON = terminating resistance used)
Serial Communications Board
(Inner Board slot 1)
Terminating resistance switch
Set to ON (right position).
Two-wire/four-wire switch
For RS-422A: Set to 4 to
use four-wire (right position).
Connecting a CS-series CPU Unit
When a CS-series CPU Unit is connected, settings are required in the PLC Setup and on the
front-panel switches of the CPU Unit.
PLC Setup
There are two methods that can be used to change the parameters in the PLC Setup.
• CX-Programmer
• Programming Console
Using the CX-Programmer
Precautions
for Safe Use
If one or more parameters in the PLC Setup in the CPU Unit has been previ-
ously changed, always upload the PLC Setup from the CPU Unit and make any
new changes in the uploaded copy so that you do not overwrite the previous
changes.
1. Open the project file in the CX-Programmer and select PLC - PLC Information - PLC
Settings from the menus.
2. The PLC Settings Dialog Box will be displayed. Click the tab for the port to which the PT
is connected and change the following three parameters. (The following screen capture
is provided as an example. The parameters that are actually displayed will depend on
the model of the CPU Unit and the port.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NS - SETUP and is the answer not in the manual?

Omron NS - SETUP Specifications

General IconGeneral
BrandOmron
ModelNS - SETUP
CategoryTouch terminals
LanguageEnglish

Related product manuals