EasyManua.ls Logo

Omron NX102-12 Series

Omron NX102-12 Series
578 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration
1
Configuration
2
Configuration
3
OMRON error code
01 0810 Error code returned from target:
The latest data cannot be retrieved from
the CPU Unit after a connection was
opened. (Automatic recovery by connec-
tion open retry)
It occurs when
the CPU Unit
task period is
too long after a
connection was
opened or
when the con-
troller system
stopped due to
an error on the
controller
.
If it occurred
due to a long
task period, the
error will be re-
covered auto-
matically. If it
was caused by
stoppage of the
controller sys-
tem, the cause
of the error will
be identified
from the error
information of
the CPU Unit.
The meaning
of this error
code is defined
by each ven-
dor, so it de-
pends on the
target's specifi-
cations.
(Contact the
target device's
manufacturer.)
The meaning of
this error code
is defined by
each vendor,
so it depends
on the origina-
tor's specifica-
tions.
(Contact the
originator devi-
ce's manufac-
turer.)
01 0811 Error code generated by originator:
The latest data cannot be retrieved from
the CPU Unit after a connection was
opened. (Automatic recovery by connec-
tion open retry)
It occurs when
the CPU Unit
task period is
too long after a
connection was
opened.
If the task peri-
od was too
long, operation
recovers auto-
matically
.
The meaning
of this error
code is defined
by each ven-
dor, so it de-
pends on the
target's specifi-
cations.
(Contact the
target device's
manufacturer.)
The meaning of
this error code
is defined by
each vendor,
so it depends
on the origina-
tor's specifica-
tions.
(Contact the
originator devi-
ce's manufac-
turer.)
16 Troubleshooting