Overview of Analog I/O Units Section 5-1
Analog Output Units
Note In 0- to 20-mA mode, accuracy cannot be ensured at 0.2 mA or less.
Moving average Supported. (Set using Setting Tool.) Supported. (Set using DeviceNet Config-
urator.)
Off-wire detection Supported.
Scaling, offset compensation, peak/
bottom hold, top/valley hold, rate of
change operations, comparator,
user adjustment (maintenance func-
tion), cumulative counter (mainte-
nance function), last maintenance
date (maintenance function)
Supported. (Set using Setting Tool.) Supported. (Set using DeviceNet Config-
urator.)
Unit GRT1 Series DRT2 Series
Model GRT1-DA2V
(Voltage Output)
GRT1-DA2C
(Current Output)
DRT2-DA02
Analog points 2 outputs
Output signal range 0 to 5 V, 1 to 5 V, 0 to 10
V, –10 to 10 V
0 to 20 mA, 4 to 20 mA 0 to 5 V, 1 to 5 V, 0 to 10 V, –10
to 10 V, 0 to 20 mA, 4 to 20 mA
Conversion time 2 ms/2 points
DA conversion data 0 to 5 V, 1 to 5 V, 0 to
10 V: 0000 to 1770 hex
–10 to 10 V: F448 to
0BB8 hex
Note Two’s complement
0 to 20 mA, 40 to 20 mA:
0000 to 1770 hex
Note Two’s Comple-
ment
0 to 5 V, 1 to 5 V, 0 to 10 V, 0 to
20 mA, 4 to 20 mA: 0000 to 1770
hex
–10 to 10 V: F448 to 0BB8 hex
Note Two’s complement
Resolution 1/6,000 (full scale)
Unit power supply Supplied by slice bus. Supplied by communications
power supply.
Communications power sup-
ply current consumption
None 120 mA max.
Overall accuracy 25°C
±0.4% FS ±0.4% FS (See note.)
Voltage output: ±0.3% FS
Current output: ±0.4% FS
10 to
55°C
±0.8% FS ±0.8% FS (See note.)
Voltage output: ±0.6% FS
Current output: ±0.8% FS
Data allocated in I/O Only Analog output values for 2 outputs Default: Analog output values for
2 points
The DeviceNet Configurator can
be used to allocate Generic Sta-
tus Flags.
Output range switching Set using the DIP switch or Setting Tool. Set using the DIP switch or the
DeviceNet Configurator.
Node address setting No setting required. Set using the rotary switches or
the DeviceNet Configurator.
Baud rate setting No setting required. Automatically detected: Uses the
baud rate set for the Master Unit.
Communications error output Set using the Setting Tool. Set using the DeviceNet Config-
urator.
Scaling, user adjustment
(maintenance function), cumu-
lative counter (maintenance
function), last maintenance
date (maintenance function)
Supported. (Set using the Setting Tool.) Supported. (Set using the
DeviceNet Configurator.)
Unit GRT1 Series DRT2 Series
Model GRT1-AD2 DRT2-AD04