188
Temperature Input Units Section 6-4
3. Open the tab page for the input for which temperature data is to be select-
ed, and select from the pull-down list the type of data to be allocated as the
Temperature Data.
4. Return to the General Tab Page, click the Download Button, and then
click the Reset Button to reset the Unit.
5. Click the OK Button to exit.
6-4-4 Functions and Settings
Moving Average
Processing
This function calculates the average value (moving average) of the previous
eight inputs, and uses the resulting value as conversion data. When the input
value fluctuates frequently, averaging can be used to produce a stable input
value, as shown in the following diagram.
Setting Procedure (Example: DeviceNet Configurator)
1,2,3... 1. In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select Pa-
rameters - Edit. The Edit Device Parameters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the I/O Module Tab
Page.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
Temperature input value
Actual input
Averaged input
Time