12
Specifications Shared by the Units Section 2-1
2-1 Specifications Shared by the Units
2-1-1 General Specifications
2-1-2 Slice I/O Unit Specifications
2-1-3 LED Indicators
The following table shows the meaning of the Unit’s TS and I/O indicators,
which are common to all of the Slice I/O Units.
The ERR indicators show errors specific to the Unit, such as I/O errors. Any
numbers that immediately follow “ERR” indicate the channel number, e.g.
ERR0 indicates a Unit that has an error in channel 0.
Item Specification
Ambient operating temperature
−10 to 55
°C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Ambient storage temperature
−25 to 65
°C (with no icing or condensation)
Noise immunity Conforms to IEC61000-4-4, 2.0 kV
Vibration resistance 10 to 60 Hz: 0.7 mm double amplitude
60 to 150 Hz: 50 m/s
2
Shock resistance
150 m/s
2
Withstand voltage 500 VAC (between isolated circuits)
Enclosure rating IP20
Item Specification
Communications protocol Slice bus
Communications distance Slice I/O Units: 64 Units coupled (about 2 m max.)
Turnback Cable: 2 m max. (2 cables, 1 m each)
Unit power supply Voltage: 24 VDC
Unit connection method Building-block style configuration with slide connec-
tors on sides of Units
Unit number 1 to 64 (automatically allocated)
I/O power supply Voltage: 24 VDC
Current: 4 A max.
Indicators TS
(Two-color LED)
Indicates the Unit’s operating status
IO
(One-color LED)
Indicates the I/O status