137
Analog Output Units Section 5-5
The following table shows the additional time required for each function
(unit: ms).
Calculation Example When using two points, and applying scaling to the first input, and the cumula-
tive counter to the second input, the maximum AD conversion cycle time can
be obtained by using the following formula.
Formula: 2.42 + 0.055 + 0.035 = 2.51 ms
5-5 Analog Output Units
5-5-1 GRT1-DA2C/GRT1-DA2V Analog Output Units
General Specifications
Performance Specifications
Math operation Additional time for each point
Moving average 0.045
Scaling 0.055
Peak/bottom hold 0.025
Top/valley hold 0.070
Comparator 0.065
Rate of change 0.030
Cumulative counter 0.035
Item Specifications
Unit power supply voltage 24 VDC (24 VDC −15% to +10%)
I/O power supply voltage I/O power supply not required.
Noise immunity Conforms to IEC 61000-4-4. 2.0 kV (power lines)
Vibration resistance
10 to 60 Hz, 0.7-mm double amplitude; 60 to 150 Hz, 50 m/s
2
Shock resistance
150 m/s
2
Dielectric strength 500 VAC for 1 min. with 1-mA sensing current (between communications
and analog circuits)
Ambient temperature –10 to 55°C (with no icing or condensation)
Ambient humidity 25% to 85% (with no condensation)
Operating environment No corrosive gases
Storage temperature –25 to 65°C (with no icing or condensation)
Mounting 35-mm DIN Track mounting
Item Specifications
GRT1-DA2V Voltage output GRT1-DA2C Current output
Output points 2 points (outputs 0 and 1)
Output type 0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
0 to 20 mA
4 to 20 mA
Output range setting method • DIP switch: Outputs 0 and 1 set separately.
• Setting Tool: Outputs 0 and 1 set separately.
External output allowable load resistance 5 kΩ min. 350 Ω max.
Resolution 1/6,000 (full scale)
Overall accuracy 25°C ±0.4% FS ±0.4% FS (See note.)
–10 to 55°C ±0.8% FS ±0.8% FS (See note.)
Conversion time 2 ms/2 points