52
Functions of Digital I/O Units Section 4-4
4-4-3 Sensor Power ON Delay (Input Units Only)
Function Overview When the I/O power has gone OFF, this function blocks inputs for the first 100
ms after the I/O power is turned back ON. The power ON delay allows the
sensor power supply to stabilize and prevents false input signals caused by
inrush current at startup. The Programming Device can be used to enable or
disable this function.
Setting with a
Programming Device
This example shows how to use the DeviceNet Configurator (version 2.43 or
higher) to set the sensor power ON delay function.
1,2,3... 1. Open the Network Configuration Window and double-click the desired
Slice I/O Terminal’s icon or right-click the icon and select Parameters -
Edit to display the Edit Device Parameters Window.
2. Select the desired Slice I/O Unit from the list on the I/O Module Tab Page
and click the Edit Button to display the Edit Unit Parameters Window.
3. Select the IN Tab, select the Enable Option for the Sensor Power ON De-
lay, and click the OK Button.
4. Click the General Tab.
5. Click the Download Button, and then click the Reset Button to reset the
Unit.
6. Click the OK Button.