17
Functions Shared by all Units Section 2-3
Input Data Patterns and Sizes
Output Data Patterns and
Sizes
(1) Only one pattern of output data can be allocated.
(2) When allocating data, be sure that it does not exceed the maximum that
can be allocated (64 words).
2-3 Functions Shared by all Units
2-3-1 Backup Function
Function Overview The backup function records the parameter data of all Slice I/O Units con-
nected to the Communications Unit. The parameter data recorded in the
Communications Unit can be restored to the Slice I/O Units later with the
automatic restore function when a Slice I/O Unit has been replaced.
Backup Procedure when
using a DeviceNet
Communications Unit
1,2,3... 1. Verify that the power is ON, DIP switch pin 1 (REGS) is ON, and all of the
Slice I/O Units are participating in I/O communications.
Allocated data pattern Description
1. Input data + Communications
Unit Status Flags
Used input data size + 1 word
Maximum Input Area: 65 words (with Communica-
tions Unit)
2. Input data only The total of the bit, word, and used areas. Calcu-
late following the previous example.
Maximum Input Area: 64 words (with Communica-
tions Unit)
3. Communications Unit Status
Flags only
1 word (with Communications Unit)
4. Slice I/O Unit Communica-
tions Participating/Withdrawn
Flags only
Participating Flags: 4 words
Withdrawn Flags: 4 words
Total: 8 words
Allocated data pattern Description
Output data only The total of the bit, word, and used areas. Calcu-
late following the previous example.
Maximum Input Area: 64 words (with Communica-
tions Unit)
Communications
Unit
Turn pin 4 ON, OFF, and
then ON again while the
power is ON and pin 1 is ON.
Downloads all of the I/O Units' unit
information and parameter data.
#1
#2 #3 #4
Power ON