167
Temperature Input Units Section 6-4
Note (1) When a result value exceeds the monitoring set value, a red alarm icon
will be displayed to the left of the comparison number.
(2) When either of the comparison inputs is disconnected (off-wire detected),
the result value will be set to 0.00 and a yellow alarm icon will be dis-
played to the left of the comparison number.
Error History Tab
Page
For details on the Error History Tab Page, refer to 4-5-1 Checking Mainte-
nance Information.
6-4 Temperature Input Units
6-4-1 GRT1-TS2@ Temperature Input Units
General Specifications
Item Description
Comparison
Description
Displays the inputs used in the error calculation.
Result Value Displays the calculation results.
Item Specifications
Model GRT1-TS2P/-TS2PK/-TS2T
Unit power supply voltage 24 VDC (24 VDC –15% to +10%)
I/O power supply voltage I/O power supply not required.
Noise immunity Conforms to IEC 61000-4-4. 2.0 kV (power lines)
Vibration resistance 10 to 60 Hz, 0.7-mm double amplitude, 60 to 150 Hz,
50 m/s
2
Shock resistance
150 m/s
2
Dielectric strength 500 VAC for 1 min. with 1-mA sensing current
(between isolated circuits)
Ambient temperature –10 to 55°C (with no icing or condensation)
Ambient humidity 25% to 85%
Operating environment No corrosive gases
Storage temperature –25 to 65°C (with no icing or condensation)
Mounting 35-mm DIN Track mounting