EasyManua.ls Logo

Omron SmartSlice GRT1 Series

Omron SmartSlice GRT1 Series
366 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
166
Maintenance Information Window Section 6-3
Display Area
Status Check Boxes
Data Comparison
between Channels
Tab Page
Each comparison number (No.) corresponds to the comparison of a pair of
inputs.
Item Description
Input Type Shows the present input type.
Display Mode Indicates the number of digits displayed.
0000: No decimal point. (GRT1-TS2T only)
0000.0: Displays to the 10ths place (0.1).
0000.00: Displays to the 100ths place (0.01).
I/O Comment Displays up to 32 characters of text as a comment. A separate
comment can be set for each input.
Last Maintenance
Date
Displays the last maintenance date and time.
Present Value Displays the present temperature input value.
Displays data derived from the temperature input value,
including the Peak Value, Bottom Value, Top Value, Valley
Value, Rate of Change, Temperature Range Total Time,
Top/Valley Count, Cumulated Count, Maximum Value, and
Minimum Value.
For details, refer to the descriptions of individual functions and
setting methods.
Item Description
Threshold Cumu-
lated Counter Over
ON when the cumulative counter value exceeds the set value.
Cumulated Counter
Overflow
ON when there is an overflow in the cumulative counter value.
Cumulated Counter
Underflow
ON when there is an underflow in the cumulative counter
value.
Over Range/Under
Range
ON when the temperature data is above or below the display-
able range.
Alarm Over/Warning
Over
ON when the analog data is above or below the monitoring set
values set in the comparator function.
Broken wire ON when a wire is broken or disconnected.
Temperature Range
Total Time Over
ON when the present value being counted in the set range
exceeds the monitoring set value.
Top/Valley Count
Over
ON when the top or valley count exceeds the monitoring set
value.
User Adjustment ON when the user-set adjustment function is operating.

Table of Contents