EasyManua.ls Logo

Omron SmartSlice GRT1 Series

Omron SmartSlice GRT1 Series
366 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
168
Temperature Input Units Section 6-4
Performance Specifications
GRT1-TS2P/TS2PK
Note For the GRT1-TS2P, a current of 0.35 mA flows to the platinum re-
sistance thermometer. For the GRT1-TS2PK, a current of
0.035 mA flows to the platinum resistance thermometer.
Note A 2-wire connection has a strong affect on the conductor resistance. When
using a 2-wire connection, the conductor resistance R directly determines the
error.
GRT1-TS2P: The error will be 4°C/Ω for each line. For example, when using a
conductor with a resistance R of 1 Ω, the total conductor resistance would be
1 Ω × 2 = 2 Ω. Therefore, an error of 4°C/Ω × 2 Ω = 8.0°C would occur.
GRT1-TS2PK: The error will be 0.4°C/Ω for each line. For example, when
using a conductor with a resistance R of 1 Ω, the total conductor resistance
would be 1 Ω × 2 = 2 Ω. Therefore, an error of 0.4°C/Ω × 2 Ω = 0.8°C would
occur.
Item Specifications
Model GRT1-TS2P GRT1-TS2PK
Input Platinum resistance thermometer
Number of I/O points 2 inputs (Two input words are allocated in the Master
when normal display mode is selected or 4 input
words are allocated when 1/100 display mode is
selected.)
Input type
PT100 (
200 to 850°C) or
PT100 (200 to 200°C);
switching possible.
Using Setting Tool: Can
be set separately for each
input.
Using DIP switch: Both
inputs are set together.
PT1000 (
200 to 850°C)
or PT1000 (200 to
200°C); switching possi-
ble.
Using Setting Tool: Can
be set separately for each
input.
Using DIP switch: Both
inputs are set together.
Indication accuracy
200 to 850°C input range:
(±0.3% of indication value or ±0.8
°C, whichever is
larger) ±1 digit max.
200 to 200°C input range:
(±0.3% of indication value or ±0.5°C, whichever is
larger) ±1 digit max.
Conversion cycle 250 ms/2 points
Temperature conversion data Binary data two's complement (4-digit hexadecimal
when normal display mode is selected or 8-digit hexa-
decimal when 1/100 display mode is selected)
Isolation method Between input and communications lines: Photocou-
pler isolation
Between temperature input signals: Photocoupler iso-
lation

Table of Contents

Related product manuals