96
Status Areas Section 5-2
Alarm Status Area The Analog Input Unit’s Alarm Status Area is configured of the following 16
bits. The Alarm Status Area provides notification of serious errors detected in
the Unit.
GRT1-DA2@
Warning Status Area The Analog Output Unit’s Warning Status Area is configured of the following
16 bits. The Warning Status Area provides notification of minor errors
detected in the Unit.
9 Cumulative Counter Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the cumulative value
exceeds the monitoring set value.
10 Reserved. ---
11 Reserved. ---
12 Reserved. ---
13 Reserved. ---
14 Reserved. ---
15 Reserved. ---
Bit Contents Description
Bit Contents Description
0 Reserved. ---
1 EEPROM data error OFF: Normal; ON: Error
2 Reserved. ---
3 Reserved. ---
4 Reserved. ---
5 Reserved. ---
6 Reserved. ---
7 Reserved. ---
8 Off-wire Detection Flag OFF: Normal; ON: Disconnection
9 Analog hardware error OFF: Normal; ON: Error in analog hard-
ware
10 Reserved. ---
11 Reserved. ---
12 Reserved. ---
13 Reserved. ---
14 Reserved. ---
15 Reserved. ---
Bit Contents Description
0 Reserved. ---
1 Reserved. ---
2 Reserved. ---
3 Unit Maintenance Flag
OFF: Normal; ON: Error (over
threshold)
Monitors the power-ON time set as the
threshold for the Unit conduction time
monitoring function.
4 Reserved. ---
5 Reserved. ---
6 Reserved. ---
7 Reserved. ---