100
Analog Input Units Section 5-4
Performance Specifications
Storage temperature –25 to 65°C (with no icing or condensation)
Mounting 35-mm DIN Track mounting
Item Specifications
Voltage input Current input
Input points 2 points (inputs 0 to 1)
Input signal range 0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
0 to 20 mA
4 to 20 mA
Input range setting method • DIP switch: Inputs 0 and 1 share the same setting.
• Setting Tool: Inputs 0 to 1 can be set separately.
Maximum signal input ±15 V ±30 mA
Input impedance 1 M Ω min. Approximately 250 Ω
Resolution 1/6,000 (full scale)
Overall accuracy 25°C ±0.3% FS ±0.4% FS
–10 to 55°C ±0.6% FS ±0.8% FS
Analog conversion cycle 2 ms max./2 points (when math operations are not used)
AD conversion data –10 to 10 V range: F448 to 0BB8 hex full scale (–3,000 to 3,000)
Other ranges: 0000 to 1770 hex full scale (0 to 6,000)
AD conversion range: ±5% FS of the above data ranges.
Isolation method Photocoupler isolation (between input and communications lines)
No isolation between input signal wires
I/O connection method Screwless Terminal block
Item Specifications