102
Analog Input Units Section 5-4
Input Range Settings
■ Inputs 0 and 1 (Shared Setting)
Setting Tool Procedure (Example: DeviceNet Configurator)
1,2,3... 1. In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select Parameters - Edit. The Edit Device Parameters
Window will be displayed.
2. Click the I/O Module Tab.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the input where the range is to be changed.
5. Select the desired range from the pull-down menu in the Input Range
Field.
6. Return to the General Tab Page, click the Download Button, and then
click the Reset Button to reset the Unit.
7. Click the OK Button to exit the window.
Input range Pin 1 Pin 2 Pin 3
0 to 5 V OFF OFF OFF
1 to 5 V ON OFF OFF
0 to 10 V OFF ON OFF
–10 to 10 V ON ON OFF
4 to 20 mA OFF OFF ON
0 to 20 mA ON OFF ON
Cannot set for other ranges. --- --- ---