Analog Input Units Section 5-4
ages are expressed as two’s complements (16 bits). When a disconnection
occurs, the data equivalent to 0 V input will be used (0000 hex).
Input Range:1 to 5 V
The voltage range 1 to 5 V corresponds to 0000 to 1770 hex (0 to 6,000). The
convertible data range is FED4 to 189C hex (
300 to 6,300). If the input volt-
age falls below the input range (input voltage less than 0.76 V), a disconnec-
tion is detected and the data is set to 7FFF hex.
Input Range: 0 to 10 V
The voltage range 0 to 10 V corresponds to 0000 to 1770 hex (0 to 6,000).
The convertible data range is FED4 to 189C hex (
300 to 6,300). Negative
voltages are expressed as two’s complements (16 bits). When a disconnec-
tion occurs, the data equivalent to 0 V input will be used (0000 hex).
189C (6300)
1770 (6000)
0000 (0)
0 V
FED4 (300)
0.25 V
5 V
5.25 V
Conversion data
Hexadecimal (decimal)
Voltage
189C (6300)
1770 (6000)
FED4 (300)
0000 (0)
1 V
0.8 V
5 V 5.2 V
7FFF
0.76 V
(Disconnection detected below 0.76 V.)
Conversion data
Hexadecimal (decimal)
Voltage
Clamped
above 5.2 V.
189C (6300)
1770 (6000)
0000 (0)
0 V
FED4 (300)
0.5 V
10 V 10.5 V
Conversion data
Hexadecimal (decimal)
Voltage