116
Analog Input Units Section 5-4
Setting Procedure (Example: DeviceNet Configurator)
1,2,3... 1. In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Analog Input Unit that is to be set. Alternatively, right-
click the icon and select Parameters - Edit. The Edit Device Parameters
Window will be displayed.
2. Click the I/O Module Tab.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the input where scaling is to be performed, and se-
lect the Scaling Check Box in the Function Choice Area.
Upper limit 7FFE
100% scaling value
Scaled line
0% scaling
Offset value
(–28,000 to
28,000)
Input signal range
0%
100%