133
Analog Input Units Section 5-4
DRT2-AD2
Setting Procedure (Example: DeviceNet Configurator)
1,2,3... 1. In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select Parameters - Edit. The Edit Device Parameters
Window will be displayed.
2. Click the I/O Module Tab.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the input where the cumulative counter is to be set,
and select the Cumulated Count Check Box in the Function Choice Area.
Unit Divisions
Hour 3.6 s (1/1,000 hour)
Minute 60 ms (1/1,000 minute)