139
Analog Output Units Section 5-5
■ GRT1-DA2C
Each pin is set according to the following table.
Setting Using the
DeviceNet Configurator
Use the following procedure to set the output range for each output using the
Configurator.
1,2,3... 1. In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select Parameters - Edit. The Edit Device Parameters
Window will be displayed.
2. Click the I/O Module Tab.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the output where the range is to be changed.
3 Reserved Fixed at OFF.
4 Set the range setting method. OFF: Set using Setting Tool.
ON: Set using DIP switch.
Default setting: OFF
Output range Pin 1 Pin 2 Pin 3
0 to 5 V (Factory set-
ting)
OFF OFF Fixed at OFF.
1 to 5 V ON OFF
0 to 10 V OFF ON
–10 to 10 V ON ON
Pin No. Setting Specifications
Pin No. Setting Specifications
1 Set output range for Outputs 0
and 1.
Default setting: All pins OFF
2 Reserved Fixed at OFF.
3
4 Range setting method OFF: Set using Setting Tool.
ON: Set using DIP switch.
Default setting: OFF
Output range Pin 1 Pin 2 Pin 3
4 to 20 mA OFF Fixed at OFF.
0 to 20 mA ON