Analog Output Units Section 5-5
Output Range: 0 to 20 mA The values 0000 to 1770 hex (0 to 6,000) correspond to the current range 0 to
20 mA. The output range is 0 to 21 mA.
DA Conversion Data DA conversion data is output to the Communications Unit as shown in the fol-
lowing diagram.
When outputting negative voltages, specify the DA conversion data as two’s
complements. The NEG instruction can be used to obtain two’s complements
from absolute values.
Note Although the number of DA conversion points is set from the Setting Tool, the
allocated data does not change (i.e., two words are used).
Dimensions
189C
(6300)
1770
(6000)
0000 (0)
0 mA
21 mA
20 mA
FFFF
7FFF
Conversion data
Hexadecimal (decimal)
Current