Application Precautions 5
Be sure that all the terminal screws are tightened to the torque specified
in the relevant manuals. Loose screws may cause fire, malfunction, or
damage the Unit.
Be sure that all the mounting screws and cable connector screws are
tightened to the torque specified in the relevant manuals.
Be sure that all the communications connector screws are tightened
securely. (The communications connector screw torque is 0.5 to
0.6 N·m.)
Use the correct wiring components when wiring.
Use crimp terminals for wiring. Do not connect bare stranded wires
directly to terminals.
Double-check all wiring before turning ON the power supply.
When wiring or performing other tasks, do not allow metal objects such as
wire strands to enter the Unit.
Always follow the electrical specifications for terminal polarity, communi-
cations path wiring, power supply wiring, and I/O jumpers. Incorrect wiring
can cause failures.
Always wire the Unit as shown in the manual.
Be sure to press terminals until they are fully seated.
Mount Units only after checking terminal blocks completely.
Before mounting a wired terminal block to the main block, be sure that the
terminal block-main block combination is correct.
Be sure that the communications cable connectors and other items with
locking devices are properly locked into place.
Do not drop the Unit or subject the Unit to excessive vibration or shock.
Doing so may cause malfunction or damage to the Unit.
Use the special packing box when transporting the Unit. Ensure that the
product is handled carefully so that no excessive vibration or impact is
applied to the product during transportation.
Check the user program for proper execution before actually running it
with the system.
Do not bend or pull the cables excessively.
When connecting communications cables, always turn OFF the PLC
power supply, all Slave power supplies, and all communications power
supplies.
Observe the following precautions when wiring the communications
cables.
Wire the communications cables separately from the power lines or
high-tension lines.
Do not bend the communications cables excessively.
Do not pull on the communications cables excessively.
Do not place objects on top of the communications cables.
Route communications cables inside ducts.
Always enable the scan list before operation.
Before clearing the scan list of a Unit that has user-allocated remote I/O,
always confirm that no errors occur after the I/O Area setting is changed
to fixed allocation.
When adding a new node to the network, check that the new node’s baud
rate is the same as the baud rate set on the other nodes.