153
Analog Output Units Section 5-5
6. To set the monitor value, click the Cumulated Count Tab, and input the
desired value in the Threshold Cumulated Counter Field.
7. Return to the General Tab Page, click the Download Button, and then
click the Reset Button to reset the Unit.
8. Click the OK Button to exit.
Setting Output Value
for Errors
The Output Unit value that is output when communications errors (timeout
and BusOff errors) or slice bus errors occur can be set in word units. The four
output value settings are set using the Setting Tool.
Setting Patterns
Output Ranges and
Values
Note When a node address has been used more than once or a Unit error has
occurred, the current output will be 0 mA and the voltage output will be 0 V,
regardless of the setting.
Low limit Outputs the values in the following table according to the output range.
High limit Outputs the values in the following table according to the output range.
Hold last state Holds and outputs the value from immediately before the error occurred.
Zero count Outputs the value when 0 is written from the Host. This setting will be affected by scaling
settings that are used.
Output range Low limit High limit Hold last state
0 to 5 V –0.25 V 5.25 V Holds value.
1 to 5 V 0.8 V 5.2 V Holds value.
0 to 10 V –0.5 V 10.5 V Holds value.
–10 to 10 V –11 V 11 V Holds value.
4 to 20 mA 3.2 mA 20.8 mA Holds value.
0 to 20 mA 0 mA 21 mA Holds value.