170
Temperature Input Units Section 6-4
The following are exceptions.
Mounting Direction
Units Supporting an Indication Accuracy of ±2°C ±1 Digit Max.
Indication Specifications Dependence on Combination of Terminal Block
and Main Block
A cold junction compensator is included in the terminal block of the
GRT1-TS2T. If only the main block is replaced, the serial numbers of the ter-
minal block and the main block will no longer match and an extra ±1°C must
be added to the indication accuracy. The serial numbers can be found on the
side of each block as shown in the following figure.
Input type Input accuracy
K, T, or N below 100°C
±7°C ±1 digit max.
U, L, or PL2
±7°C ±1 digit max.
R or S below 200°C
±7°C ±1 digit max.
B below 400°C Not specified.
W
±9°C ±1 digit max.
Slice I/O Units
GRT1-ID4
GRT1-ID4-1
GRT1-ID8
GRT1-ID8-1
GRT1-IA4-1
GRT1-IA4-2
GRT1-OD4
GRT1-OD4-1
GRT1-OD4G-1
GRT1-OD8
GRT1-OD8-1
GRT1-OD8G-1
GRT1-ROS2
GRT1-TS2P
GRT1-TS2PK
GRT1-TS2T
GRT1-CT1
GRT1-CT1-1
GRT1-CPL-1
GRT1-PD2
GRT1-PD2G
GRT1-PD8
GRT1-PD8-1
GRT1-PC8
GRT1-PC8-1
GRT1-TBR
GRT1-TBL
GRT1-END
Communications Units
GRT1-DRT
GRT1-PRT