183
Temperature Input Units Section 6-4
Using the Default
Settings
When the Temperature Input Unit’s default settings are used, only the temper-
ature input values are selected as I/O data. Two words (four bytes) are allo-
cated in the Master’s Input Area, as shown in the following diagram.
Setting Data Using a Setting Tool
Temperature data can be combined with other data, such as Status Flags, as
shown below, and allocated as I/O. The Setting Tool can be used to select the
desired data from a pull-down list.
Example: Allocating Temperature Data + Top/Valley Detection Timing Flags
The Setting Tool is used as described below to allocate data.
Setting Temperature Data (Example: DeviceNet Configurator)
1,2,3... 1. In the Network Configuration Window for the Slice I/O Terminal, dou-
ble-click the icon of the Slice I/O Terminal that is to be set. Alternatively,
right-click the icon and select Parameters - Edit. The Edit Device Param-
eters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the I/O Module Tab
Page.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
15 0
Temperature Input Value for Input 0
Temperature Input Value for Input 1
15 8 7 0
Temperature Data for Input 0
Temperature Data for Input 1
Top Detection Timing Flag Valley Detection Timing Flag