197
Temperature Input Units Section 6-4
One-shot Time Setting
1,2,3... 1. Input the desired value in the SHOT Off Delay Field of the Top/Valley Tab
Page in the Function Choice Area.
2. Return to the General Tab Page, click the Download Button, and then
click the Reset Button to reset the Unit.
3. Click the OK Button to exit.
Top/Valley Counter 
Function
This function counts the number of temperature tops or valleys in devices or
applications that have repetitive temperature rises (or drops). A threshold
value can be set for the counter to indicate when preventative maintenance is
required for the Unit or sensors. 
The Over Threshold status can be read in the Maintenance Information Win-
dow or by using an explicit message.
Valley Counter Operation
Setting Procedure (Example: DeviceNet Configurator)
1,2,3... 1. In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select Pa-
rameters - Edit. The Edit Device Parameters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the I/O Module Tab
Page.
The Valley Count function counts the number 
of valleys in the temperature input value.
Temperature 
input value
Hold value
Hold Flag
Hold function 
starts.
Hold function 
stops.
Valley hold 
value
Last value 
is held.