202
Temperature Input Units Section 6-4
Setting Procedure (Example: DeviceNet Configurator)
1,2,3... 1. In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select Pa-
rameters - Edit. The Edit Device Parameters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the I/O Module Tab
Page.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the input where the comparator function is to be set,
and select the Comparator Check Box in the Function Choice Area.
5. Click the Comparator Tab and set each of the alarm values. The example
here shows the setting for Alarm Trip Point High (HH).
Note When setting the Trip Point, adjust for each input’s decimal point position and
the 1/100 Display Mode (if it is being used). Always correct the Trip Point after
changing the display mode setting or changing to an input that has a different
decimal point position.