GRT1-CT1(-1) Counter Units Section 7-4
Encoder Z Input or Digital Input (IN)
Note The response time is the time between the moment the A, B, or Z/IN input
turns ON or OFF and the moment the digital output is updated to the new
state. The specified response time may not be achieved during monitoring or
maintenance.
Digital Output (OUT)
Note The response time is the time between the moment the A, B, Z, or IN input
turns ON or OFF and the moment the digital output is updated to the new
state. The specified response time may not be achieved during monitoring or
maintenance.
OFF current 1.0 mA max.
Maximum input signal
frequency
60 kHz for pulse/direction counter mode
60 kHz for up/down counter mode
30 kHz for phase differential counter mode (×1, ×2, or ×4)
Item Specification
Model GRT1-CT1 GRT1-CT1-1
Input type NPN PNP
Number of inputs 1
ON voltage 15.0 V min. (between input
terminal and V)
15.0 V min. (between input
terminal and G)
ON current 3.0 mA min.
OFF voltage 5.0 V max. (between input
terminal and V)
5.0 V max. (between input
terminal and G)
OFF current 1.0 mA max.
ON response time 1 ms max. (See note)
OFF response time 1 ms max. (See note)
Item Specification
Item Specification
Model GRT1-CT1 GRT1-CT1-1
Output type NPN PNP
Number of outputs 1
Total output current 500 mA max.
Residual voltage 1.2 V max. (between output
terminal and G)
1.2 V max. (between output
terminal and V)
Leakage current 0.1 mA max. 0.1 mA max.
ON response time 1 ms max. (See note)
OFF response time 1 ms max. (See note)