276
GRT1-PD2 and GRT1-PD2G I/O Power Feed Units Section 8-3
There are three methods that can be used to reset the overcurrent status of
GRT1-PD2G.
Short the RESET terminal to the V (R) terminal. The overcurrent protec-
tion function will be automatically reset.
Connect the RESET terminal to an output terminal of a Transistor Output
Unit (e.g., the GRT1-OD4-1 (PNP)) and turn ON the output signal for at
least 100 ms. If the Output Unit and I/O Power Feed Unit are connected to
different I/O power sources, ground them to the same point.
Turn the power supply OFF and ON. The overcurrent protection function
will be automatically reset.
Component Names
and Functions
LED Indicators
I/O PWR Indicator The I/O PWR indicator shows the status of the I/O power supply.
ERR Indicator The ERR indicator shows the status of the overcurrent protection function.
Reset terminals --- 1
Reset V (R) termi-
nals
--- 1
Item Specification
LED Indicators
Indicate the status of
the power supply.
Terminal block
PD2
I/O PWR
A1A2
A3A5
A4
A6
B1 B2
B3
B6B4
B5
PD2G
I/O PWR
ERR
Terminal block
LED Indicators
These indicators show
the power supply status
and the overcurrent status.
A1A2
A3A5
A4
A6
B1 B2
B3
B6B4
B5
GRT1-PD2
GRT1-PD2G
Name Color Status Meaning
I/O PWR Green Lit Normal status I/O power is being supplied nor-
mally.
--- Not lit Error status or
no power
I/O power is not being supplied
or an overcurrent occurred.
ERR Red Lit Error status An overcurrent occurred.
--- Not lit Normal status
or no power
I/O power is being supplied nor-
mally or I/O power is not being
supplied.