295
Troubleshooting by Unit Section 9-5
Troubleshooting for
Digital I/O Units
Model Details Probable cause Remedy
Digital Output Units
GRT1-OD@(-1)
GRT1-ROS2
The output is turned
ON, but no output is
performed, and the I/
O indicator is OFF.
A bus error or communications error
occurred.
Check whether there is an
error in the slice bus or host
communications.
The output is turned
ON, and the I/O indi-
cator is ON, but no
output is performed.
The I/O power is not being supplied. Check whether the I/O power
is being supplied.
Wiring with the connected device is per-
formed incorrectly.
Check the wiring with the
connected device.
Connections between the base blocks of
the Slice I/O Unit are not made properly.
(Refer to the following figure.)
Check whether the connec-
tions are made properly.
The terminal block is disconnected. Check whether the terminal
block is disconnected.
The output cannot be
held when a commu-
nications error or bus
error occurs.
The Unit's Output Hold/Clear setting is set
to clear outputs when a communications
error or bus error occurs.
Set the Unit's Output Hold/
Clear setting to hold outputs
when a communications error
or bus error occurs.
The output cannot be
cleared when a com-
munications error or
bus error occurs.
The Unit's Output Hold/Clear setting is set
to hold outputs when a communications
error or bus error occurs.
Set the Unit's Output Hold/
Clear setting to clear outputs
when a communications error
or bus error occurs.
Digital Input Units
GRT1-ID@(-1)
There is a delay in the
ON or OFF timing of
the input value.
The input filter may be set. Set the input filter value to 0
or set an appropriate value
for the input filter.
The connected device
is ON, but it is not
input and the I/O indi-
cator is not lit.
The I/O power is not being supplied. Check whether the I/O power
is being supplied.
Wiring with the connected device is per-
formed incorrectly.
Check the wiring with the
connected device.
Connections between the base blocks of
the Slice I/O Unit are not made properly.
(Refer to the following figure.)
Check whether the connec-
tions are made properly.
The terminal block is disconnected. Check whether the terminal
block is disconnected.
The connected device
is ON, and the I/O
indicator is lit, but the
Unit is not input.
A bus error or communications error
occurred.
Check whether there is an
error in the slice bus or host
communications.
The I/O power supply
connectors on the Slice I/O
Units are not interlocked
properly.
The I/O power supply
connectors on the Slice I/O
Units are not interlocked
properly.

Table of Contents